SiHF / GL-P

header edlersystems cable2 min v4
Temperaturbeständige Schlauchleitung
SiHF / GL-P

Silicone cables are used wherever cable insulation is exposed to high temperature fluctuations. Due to their excellent weather resistance, they can be used at both high and low temperatures down to -60°C. Particularly suitable for use in power stations. The insulation is tropicalised and resistant to oxygen and ozone. An outstanding property is the high flash point. When the cable is fired, an insulating silicon dioxide layer remains on the conductor, which can prevent a short circuit. The armoured braid (P) ensures a high level of mechanical protection and also provides electrical shielding.

Download datasheet (SiHF/GL-P)
Number of conductors x 
Nominal cross-section
Conductor structure Insulation thickness Outer Ø Weight Conductor resistance
at 20°C
Cu count Central warehouse Central warehouse Factory warehouse Factory warehouse
mm² approx. mm approx. mm approx. mm approx. kg/km ca. Ω/km kg/km G x G x
2 x 0,75 24 x 0,21 0,8 7,9 90,0 26,7 15,0
3 G 0,75 24 x 0,21 0,8 8,3 101,0 26,7 22,5
4 G 0,75 24 x 0,21 0,8 9,3 129,0 26,7 30,0
5 G 0,75 24 x 0,21 0,8 10,0 157,0 26,7 37,5
7 G 0,75 24 x 0,21 0,8 10,7 177,0 26,7 52,5
2 x 1 32 x 0,21 0,8 8,0 97,0 20,0 20,0
3 G 1 32 x 0,21 0,8 8,9 122,0 20,0 30,0
4 G 1 32 x 0,21 0,8 9,4 141,0 20,0 40,0
5 G 1 32 x 0,21 0,8 10,4 166,0 20,0 50,0
7 G 1 32 x 0,21 0,8 11,1 197,0 20,0 70,0
2 x 1,5 30 x 0,26 0,8 9,0 127,0 13,7 30,0
3 G 1,5 30 x 0,26 0,8 9,5 145,0 13,7 45,0
4 G 1,5 30 x 0,26 0,8 10,3 173,0 13,7 60,0
5 G 1,5 30 x 0,26 0,8 11,0 202,0 13,7 75,0
7 G 1,5 30 x 0,26 0,8 12,0 244,0 13,7 105,0
12 G 1,5 30 x 0,26 0,8 15,5 327,0 13,7 180,0
3 G 2,5 50 x 0,26 0,9 11,2 205,0 8,2 75,0
4 G 2,5 50 x 0,26 0,9 12,1 278,0 8,2 100,0
5 G 2,5 50 x 0,26 0,9 13,3 322,0 8,2 125,0
7 G 2,5 50 x 0,26 0,9 14,4 380,0 8,2 175,0
4 G 4 56 x 0,31 1,0 15,0 384,0 5,1 160,0
5 G 4 56 x 0,31 1,0 16,0 454,0 5,1 200,0
7 G 4 56 x 0,31 1,0 17,5 633,0 5,1 280,0
4 G 6 84 x 0,31 1,0 18,0 544,0 3,4 240,0
5 G 6 84 x 0,31 1,0 19,4 656,0 3,4 300,0
7 G 6 84 x 0,31 1,0 20,7 769,0 3,4 420,0

based on DIN VDE 0285-525-2-83

  • Stranded copper wire, tinned, fine stranded according to DIN VDE 0295 cl.5,
    IEC 60228 cl.5
  • Silicone wire insulation
  • Core labelling according to HD 308 S2
    from 7 core version black with numbers
  • Cores with optimum lay lengths stranded in layers
  • Common silicone sheath
  • Glass fibre braiding
  • Armoured braid made of galvanised steel wires
Nominal voltage U₀/U: 300/500 V
Testing voltage: 2000 V
Temperature range:
Operating temperature: -60°C to +180°C
Conductor operating temperature: max. +180°C
Short-circuit temperature: max. +250°C/5 sec.
Minimum bending radius:
When laying: 10 x DA
Fixed installation: 5 x DA
Fire behaviour: EN 60332-1-2
IEC 60332-1
Halogen-free: EN 60754-1
IEC 60754-1
Corrosiveness: EN 60754-2
IEC 60754-2