H05VVC4V5-K

header edlersystems cable2 min v4
Steuerleitung – harmonisiert
H05VVC4V5-K

For medium mechanical stress for flexible use with free movement without tensile stress and without forced movement guidance in dry and damp rooms. As an oil-resistant, shielded measuring, monitoring and control cable in machine tool construction, plant construction on assembly lines and production lines. Can also be used outdoors if adequately protected from direct sunlight and the temperature range is observed. This cable is not suitable for laying directly in the ground. These cables with copper shielding are ideally suited for interference-free data and signal transmission for measurement and control technology.

Download datasheet (H05VVC4V5-K)
Number of conductors x 
Nominal cross-section
Conductor Ø Insulation thickness Outer Ø (min - max)
min - max
Weight Conductor resistance
at 20°C
Cu count Central warehouse Central warehouse Factory warehouse Factory warehouse
mm² approx. mm approx. mm mm approx. kg/km ca. Ω/km kg/km G x G x
2 x 0,75 1,1 0,6 8,0 - 10,0 96,0 26,0 43,0
3 G 0,75 1,1 0,6 8,3 - 10,4 110,0 26,0 57,0
4 G 0,75 1,1 0,6 9,1 - 11,3 135,0 26,0 70,0
5 G 0,75 1,1 0,6 9,7 - 12,1 155,0 26,0 82,0
7 G 0,75 1,1 0,6 11,5 - 14,3 220,0 26,0 113,0
12 G 0,75 1,1 0,6 13,9 - 17,2 300,0 26,0 192,0
18 G 0,75 1,1 0,6 16,2 - 19,9 445,0 26,0 268,0
25 G 0,75 1,1 0,6 18,7 - 23,0 640,0 26,0 331,0
34 G 0,75 1,1 0,6 21,4 - 26,2 821,0 26,0 346,0
2 x 1 1,3 0,6 8,2 - 10,3 110,0 19,5 52,0
3 G 1 1,3 0,6 8,8 - 11,0 130,0 19,5 78,0
4 G 1 1,3 0,6 9,4 - 11,7 150,0 19,5 89,0
5 G 1 1,3 0,6 10,3 - 12,8 185,0 19,5 106,0
7 G 1 1,3 0,6 12,2 - 15,1 263,0 19,5 132,0
12 G 1 1,3 0,6 14,7 - 18,1 355,0 19,5 206,0
18 G 1 1,3 0,6 16,9 - 20,8 510,0 19,5 316,0
25 G 1 1,3 0,6 19,8 - 24,2 775,0 19,5 428,0
34 G 1 1,3 0,6 22,6 - 27,7 996,0 19,5 537,0
2 x 1,5 1,5 0,7 9,3 - 11,6 135,0 13,3 66,0
3 G 1,5 1,5 0,7 9,7 - 12,1 155,0 13,3 99,0
4 G 1,5 1,5 0,7 10,7 - 13,2 200,0 13,3 121,0
5 G 1,5 1,5 0,7 11,8 - 14,7 240,0 13,3 135,0
7 G 1,5 1,5 0,7 14,1 - 17,4 335,0 13,3 227,0
12 G 1,5 1,5 0,7 16,7 - 20,5 485,0 13,3 322,0
18 G 1,5 1,5 0,7 19,6 - 24,1 680,0 13,3 428,0
25 G 1,5 1,5 0,7 22,9 - 28,0 945,0 13,3 568,0
3 G 2,5 2,0 0,8 11,3 - 14,0 220,0 8,0 154,0
4 G 2,5 2,0 0,8 12,6 - 15,5 275,0 8,0 170,0
5 G 2,5 2,0 0,8 13,9 - 17,2 330,0 8,0 208,0
7 G 2,5 2,0 0,8 16,5 - 20,3 490,0 8,0 300,0
12 G 2,5 2,0 0,8 19,9 - 24,4 680,0 8,0 537,0
18 G 2,5 2,0 0,8 23,3 - 28,5 1.051,0 8,0 615,0
25 G 2,5 2,0 0,8 28,2 - 30,6 1.375,0 8,0 937,0

DIN VDE 0285-525-2-51

  • Bare copper stranded wire, fine stranded according to DIN VDE 0295 cl.5,
    IEC 60228 cl.5
  • PVC – core insulation TI2
  • Core labelling black with printed numbers,
    from 3 cores protective conductor green-yellow
  • Cores stranded in layers with optimum lay lengths
  • PVC inner sheath
  • Shielding braid made of tinned copper wires
  • PVC outer sheath TM5
  • Sheath colour grey (RAL 7001)
Nominal voltage U₀/U: 300/500 V
Testing voltage: 2000 V
Insulating resistance: ≥ 20 MOhm x km
Temperature range:
When laying: max. -5°C
Operating temperature: -40°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +150°C/5 sec.
Minimum bending radius:
When laying: 12,5 x DA
Fixed installation: 4 x DA
CPR performance class: Eca
Oil resistance: DIN VDE 0473-811-404
EN 60811-404