NYY - RF feindrähtig

header edlersystems cable2 min v4
Starkstromkabel 0,6/1kV
NYY - RF feindrähtig

Flexible power supply cable for fixed installation indoors, outdoors, in the ground, in water and in cable ducts if no risk of mechanical damage is to be expected.

Download datasheet (NYY feindrähtig (RF))
Number of conductors x 
Nominal cross-section
Insulation thickness Outer Ø Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C in air
Current carrying capacity
at 20°C in soil
Cu count Central warehouse Central warehouse Factory warehouse Factory warehouse
mm² approx. mm approx. mm approx. kg/km ca. Ω/km A A kg/km J O J O
1 x 16 RF 1,0 11,0 240,0 1,15 84,0 108,0 160,0
1 x 35 RF 1,2 14,0 460,0 0,524 139,0 164,0 350,0
1 x 50 RF 1,4 15,0 600,0 0,387 169,0 195,0 500,0
1 x 70 RF 1,4 17,0 800,0 0,268 213,0 238,0 700,0
1 x 95 RF 1,6 19,0 1.100,0 0,193 264,0 286,0 950,0
1 x 120 RF 1,6 21,0 1.350,0 0,153 307,0 325,0 1.200,0
1 x 150 RF 1,8 23,0 1.650,0 0,124 352,0 365,0 1.500,0
1 x 185 RF 2,0 25,0 2.000,0 0,0991 406,0 413,0 1.850,0
1 x 240 RF 2,2 27,0 2.600,0 0,0754 483,0 479,0 2.400,0
1 x 300 RF 2,4 30,0 3.200,0 0,0601 557,0 541,0 3.000,0

based on DIN VDE 0276-603/HD 603 S1

  • Bare copper conductor, fine stranded (RF)
    according to DIN VDE 0295 cl.5, IEC 60228 cl.5
  • PVC - core insulation DIV4
  • Core labelling according to HD 308 S2
  • PVC filling jacket (FM)
    or banding (BD)
  • PVC outer sheath DMV 5
  • Sheath colour black
Nominal voltage U₀/U: 0,6/1 kV
Testing voltage: 4000 V
Temperature range:
When laying: max. -5°C
Operating temperature: -30°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature:
≤ 300mm²: max. 160°C/5 sec.
> 300mm²: max. 140°C/5 sec.
Minimum bending radius:
single core: 15 x DA
multicore: 12 x DA
CPR performance class: Eca