NYBY

header edlersystems cable2 min v4
Starkstromkabel 0,6/1kV
NYBY

For increased electrical or mechanical stress for fixed installation indoors, outdoors, in the ground, in damp rooms, in concrete and in cable ducts in power stations, industrial and switchgear installations and in local networks.

Download datasheet (NYBY)
Number of conductors x 
Nominal cross-section
Insulation thickness Outer Ø Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C in air
Current carrying capacity
at 20°C in soil
Cu count Central warehouse Central warehouse Factory warehouse Factory warehouse
mm² approx. mm approx. mm approx. kg/km ca. Ω/km A A kg/km J O J O
2 x 1,5 RE 0,8 12,9 270,0 12,1 19,0 27,0 30,0
2 x 2,5 RE 0,8 13,7 315,0 7,4 25,0 36,0 50,0
2 x 4 RE 1,0 15,3 390,0 4,6 34,0 47,0 80,0
2 x 6 RE 1,0 16,3 465,0 3,1 43,0 59,0 120,0
2 x 10 RE 1,0 18,7 590,0 1,8 59,0 79,0 200,0
2 x 16 RM 1,0 20,9 790,0 1,2 79,0 103,0 320,0
2 x 25 RM 1,2 23,5 1.215,0 0,727 106,0 133,0 500,0
3 x 1,5 RE 0,8 13,4 280,0 12,1 19,0 27,0 45,0
3 x 2,5 RE 0,8 14,3 340,0 7,4 25,0 36,0 75,0
3 x 4 RE 1,0 16,0 440,0 4,6 34,0 47,0 120,0
3 x 6 RE 1,0 17,1 540,0 3,1 43,0 59,0 180,0
3 x 10 RE 1,0 19,7 710,0 1,8 59,0 79,0 300,0
3 x 16 RM 1,0 22,1 970,0 1,2 79,0 103,0 480,0
3 x 25 RM 1,2 24,9 1.463,0 0,727 106,0 133,0 750,0
3 x 35 RM 1,2 27,3 1.822,0 0,524 129,0 159,0 1.050,0
3 x 50 RM 1,4 30,7 2.356,0 0,387 157,0 188,0 1.500,0
3 x 25/16 RM 1,2/1,0 26,2 1.740,0 0,727/1,15 106,0 133,0 910,0
3 x 35/16 RM 1,2/1,0 28,2 2.340,0 0,524/1,15 129,0 159,0 1.210,0
3 x 50/25 SM/RM 1,4/1,2 31,9 2.765,0 0,387/0,727 157,0 188,0 1.750,0
3 x 70/35 SM/RM 1,4/1,2 35,8 3.590,0 0,268/0,524 199,0 232,0 2.450,0
3 x 95/50 SM 1,6/1,4 42,6 4.700,0 0,193/0,387 246,0 280,0 3.350,0
3 x 120/70 SM 1,6/1,4 45,6 5.720,0 0,153/0,268 285,0 318,0 4.300,0
3 x 150/70 SM 1,8/1,4 49,3 6.880,0 0,124/0,268 326,0 359,0 5.200,0
3 x 185/95 SM 2,0/1,6 56,1 8.440,0 0,0991/0,193 374,0 406,0 6.500,0
3 x 240/120 SM 2,2/1,6 62,4 10.880,0 0,0754/0,153 445,0 473,0 8.400,0
4 x 1,5 RE 0,8 14,2 313,0 12,1 19,0 27,0 60,0
4 x 2,5 RE 0,8 15,1 380,0 7,4 25,0 36,0 100,0
4 x 4 RE 1,0 17,1 520,0 4,6 34,0 47,0 160,0
4 x 6 RE 1,0 18,3 640,0 3,1 43,0 59,0 240,0
4 x 10 RE 1,0 21,2 860,0 1,8 59,0 79,0 400,0
4 x 16 RM 1,0 23,8 1.170,0 1,2 79,0 103,0 640,0
4 x 25 RM 1,2 27,0 1.810,0 0,727 106,0 133,0 1.000,0
4 x 35 SM 1,2 29,6 2.630,0 0,524 129,0 159,0 1.400,0
4 x 50 SM 1,4 33,6 2.940,0 0,387 157,0 188,0 2.000,0
4 x 70 SM 1,4 38,7 3.860,0 0,268 199,0 232,0 2.800,0
4 x 95 SM 1,6 45,4 5.100,0 0,193 246,0 280,0 3.800,0
4 x 120 SM 1,6 48,0 6.150,0 0,153 285,0 318,0 4.800,0
4 x 150 SM 1,8 53,0 7.510,0 0,124 326,0 359,0 6.000,0
4 x 185 SM 2,0 59,6 9.170,0 0,0991 374,0 406,0 7.400,0
4 x 240 SM 2,2 67,0 12.866,0 0,0754 445,0 473,0 9.600,0
5 x 1,5 RE 0,8 15,0 360,0 12,1 19,0 27,0 75,0
5 x 2,5 RE 0,8 16,1 436,0 7,4 25,0 36,0 125,0
5 x 4 RE 1,0 18,3 600,0 4,6 34,0 47,0 200,0
5 x 6 RE 1,0 20,0 750,0 3,1 43,0 59,0 300,0
5 x 10 RE 1,0 22,6 1.087,0 1,8 59,0 79,0 500,0
5 x 16 RM 1,0 25,8 1.472,0 1,2 79,0 103,0 800,0
7 x 1,5 RE 0,8 15,9 461,0 12,1 19,0 27,0 105,0
7 x 2,5 RE 0,8 17,1 650,0 7,4 25,0 36,0 175,0
12 x 1,5 RE 0,8 19,4 758,0 12,1 19,0 27,0 180,0
12 x 2,5 RE 0,8 21,1 970,0 7,4 25,0 36,0 300,0
14 x 1,5 RE 0,8 20,2 824,0 12,1 19,0 27,0 210,0
14 x 2,5 RE 0,8 21,9 1.035,0 7,4 25,0 36,0 350,0
16 x 1,5 RE 0,8 21,0 890,0 12,1 19,0 27,0 240,0
16 x 2,5 RE 0,8 22,9 1.170,0 7,4 25,0 36,0 400,0
19 x 1,5 RE 0,8 21,9 981,0 12,1 19,0 27,0 285,0
19 x 2,5 RE 0,8 23,9 1.300,0 7,4 25,0 36,0 475,0
24 x 1,5 RE 0,8 24,9 1.173,0 12,1 19,0 27,0 360,0
24 x 2,5 RE 0,8 27,3 1.640,0 7,4 25,0 36,0 600,0

DIN VDE 0271 and IEC 60502-1

  • Bare copper conductor, solid (SE/RE)
    according to DIN VDE 0295 cl.1, IEC 60228 cl.1
    or stranded (SM/RM)
    according to DIN VDE 0295 cl.2, IEC 60228 cl.2
  • PVC - core insulation
  • Core labelling according to HD 308 S2
    from 7 core version black with numbers
  • PVC filling coat (FM)
  • Reinforcement made of overlapping
    galvanised steel strip
  • PVC outer sheath
  • Sheath colour black
Nominal voltage U₀/U: 0,6/1 kV
Testing voltage: 4000 V
Temperature range:
When laying: max. -5°C
Operating temperature: -30°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +160°C/5 sec.
Minimum bending radius:
single core: 15 x DA
multicore: 12 x DA
CPR performance class: Eca