E-YCY-O

header edlersystems cable2 min v4
Starkstromkabel 0,6/1kV
E-YCY-O

For industrial and switchgear applications, house connections and street lighting as well as control cables for transmitting control pulses and measured values. For increased electrical and mechanical stress for fixed installation indoors, outdoors, in the ground, in water, concrete and in cable ducts. The concentric conductor (C) may be used as a PE or PEN conductor or as a shield.

Download datasheet ( E-YCY/16)
Number of conductors x 
Nominal cross-section
Insulation thickness Outer Ø Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Current carrying capacity
at 20°C in soil
Cu count Central warehouse Central warehouse
mm² approx. mm approx. mm approx. kg/km ca. Ω/km A A kg/km J O
2 x 4 RE/16 1,0 14,7 432,0 4,6 37,0 54,0 270,0
4 x 1,5 RE/16 0,8 14,0 367,0 12,1 19,5 27,0 250,0
4 x 2,5 RE/16 0,8 15,0 419,0 7,4 25,0 36,0 290,0
4 x 4 RE/16 1,0 16,0 542,0 4,6 34,0 46,0 350,0
4 x 6 RE/16 1,0 17,6 639,0 3,1 43,0 58,0 430,0
4 x 10 RE/16 1,0 19,6 856,0 1,8 59,0 78,0 590,0
4 x 10 RM/16 1,0 20,6 883,0 1,8 59,0 78,0 590,0
5 x 2,5 RE/16 0,8 15,4 462,0 7,4 19,5 25,0 315,0
5 x 4 RE/16 1,0 17,9 607,0 4,6 25,5 32,0 390,0
5 x 6 RE/16 1,0 19,3 726,0 3,1 32,0 41,0 490,0
5 x 10 RE/16 1,0 22,7 1.013,0 1,8 44,0 55,0 690,0
5 x 10 RM/16 1,0 23,7 1.040,0 1,8 44,0 55,0 690,0
5 x 16 RE/16 1,0 25,0 1.375,0 1,2 59,0 71,0 990,0
5 x 16 RM/16 1,0 26,0 1.410,0 1,2 59,0 71,0 990,0
7 x 1,5 RE/16 0,8 17,8 449,0 12,1 12,5 16,0 295,0
7 x 2,5 RE/16 0,8 18,8 572,0 7,4 17,0 21,5 365,0
7 x 4 RE/16 1,0 19,1 774,0 4,6 22,0 27,5 470,0
10 x 1,5 RE/16 0,8 18,1 588,0 12,1 10,5 13,5 340,0
10 x 2,5 RE/16 0,8 19,9 742,0 7,4 14,5 18,0 440,0
12 x 1,5 RE/16 0,8 17,6 613,0 12,1 10,0 12,5 370,0
12 x 2,5 RE/16 0,8 20,4 847,0 7,4 13,5 17,0 490,0
14 x 1,5 RE/16 0,8 19,2 676,0 12,1 9,5 12,0 400,0
14 x 2,5 RE/16 0,8 21,4 922,0 7,4 13,0 16,0 540,0
19 x 1,5 RE/16 0,8 20,9 808,0 12,1 9,0 11,0 475,0
19 x 2,5 RE/16 0,8 24,0 1.188,0 7,4 11,5 14,5 665,0
24 x 1,5 RE/16 0,8 24,2 1.041,0 12,1 8,0 9,5 550,0
24 x 2,5 RE/16 0,8 27,4 1.308,0 7,4 10,5 12,5 790,0
30 x 1,5 RE/16 0,8 25,5 1.119,0 12,1 7,5 8,5 640,0
30 x 2,5 RE/16 0,8 28,7 1.670,0 7,4 9,5 11,5 940,0

ÖVE K 23 and K 603/HD 603 S1
from 7 cores K 627/HD 627 S1

  • Bare copper conductor, solid (RE)
    accroding to EN 60228 cl.1, or stranded (RM)
    according to  EN 60228 cl.2
  • PVC - core insulation
  • Core labelling according to HD 308 S2
    from 7 cores black with numbers
  • PVC filler jacket (FM) or strapping (BD)
  • Concentric conductor, round copper wires between
    sheath and outer sheath, copper tape as cross
    copper tape over the copper wires
  • PVC - outer sheath
  • Sheath colour black
Nominal voltage U₀/U: 0,6/1 kV
Testing voltage: 4000 V
Temperature range:
When laying: max. -5°C
Operating temperature: -30°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +160°C/5 sec.
Minimum bending radius: 12 x DA
CPR performance class: Eca