E-XYCY-O

header edlersystems cable2 min v4
Starkstromkabel 0,6/1kV
E-XYCY-O

For industrial and switchgear applications and as a control cable for transmitting control pulses and measured values. For increased electrical and mechanical stress for fixed installation indoors, outdoors, in the ground, in water, concrete and in cable ducts. The concentric conductor (C) may be used as a PE or PEN conductor or as a shield.

Download datasheet (E-XYCY/16)
Number of conductors x 
Nominal cross-section
Insulation thickness Outer Ø Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Current carrying capacity
at 20°C in soil
Cu count Central warehouse
mm² approx. mm approx. mm approx. kg/km ca. Ω/km A A kg/km O
3 x 2,5 RE/16 0,8 12,9 385,0 7,4 25,0 36,0 283,0
4 x 1,5 RE/16 0,8 14,4 395,0 12,1 19,5 27,0 275,0
4 x 2,5 RE/16 0,8 15,4 437,0 7,4 25,0 36,0 315,0
4 x 4 RE/16 1,0 16,4 566,0 4,6 34,0 46,0 395,0
4 x 6 RE/16 1,0 18,0 654,0 3,1 43,0 58,0 467,0
4 x 10 RE/16 1,0 20,0 879,0 1,8 59,0 78,0 635,0
4 x 16 RE/16 1,0 22,6 1.189,0 1,2 78,0 101,0 889,0
5 x 2,5 RE/16 0,8 15,8 478,0 7,4 19,5 25,0 347,0
5 x 4 RE/16 1,0 18,3 631,0 4,6 25,5 32,0 435,0
5 x 6 RE/16 1,0 19,7 748,0 3,1 32,0 41,0 535,0
5 x 10 RE/16 1,0 23,1 1.052,0 1,8 44,0 55,0 735,0
5 x 16 RE/16 1,0 25,4 1.405,0 1,2 59,0 71,0 1.049,0
7 x 1,5 RE/16 0,8 18,2 462,0 12,1 12,5 16,0 325,0
7 x 2,5 RE/16 0,8 19,2 585,0 7,4 17,0 21,5 400,0
12 x 1,5 RE/16 0,8 18,0 627,0 12,1 10,0 12,5 395,0
12 x 2,5 RE/16 0,8 20,8 863,0 7,4 13,5 17,0 543,0
19 x 2,5 RE/16 0,8 24,4 1.209,0 7,4 11,5 14,5 731,0
24 x 1,5 RE/16 0,8 24,6 1.064,0 12,1 8,0 9,5 620,0
30 x 1,5 RE/16 0,8 25,9 1.137,0 12,1 7,5 8,5 704,0
37 x 1,5 RE/16 0,8 28,2 1.344,0 12,1 7,0 8,0 827,0
61 x 1,5 RE/16 0,8 33,8 1.994,0 12,1 6,0 7,0 1.219,0

based on DIN VDE 0276-603/HD 603 S1
from 7 cores DIN VDE 0276-267/HD 627 S1
and according to APG regulation

  • Bare copper conductor, solid (RE)
    according to DIN VDE 0295 cl.1, IEC 60228 cl.1
  • PVC - core insulation
  • Core labelling according to HD 308 S1
    from 7 cores black with numbers
  • PVC - Filling coat (FM)
  • Concentric conductor, round copper wires between
    core sheath and outer sheath,
    Copper tape winding 3-5 mm
    overlapping over the copper wires
  • PVC - outer sheath
  • Sheath colour black
Nominal voltage U₀/U: 0,6/1 kV
Testing voltage: 4000 V
Temperature range:
When laying: max. -5°C
Operating temperature: -30° to +70°C
Conductor operating temperature: max. +70 °C
Short-circuit temperature: max. +160°C/5 sec.
Minimum bending radius: 12 x DA
CPR performance class: Eca