E-AYY

header edlersystems cable2 min v4
Starkstromkabel 0,6/1kV
E-AYY

As power supply cables for power stations, industry and switchgear, as well as in local networks. For fixed installation indoors, outdoors, in the ground, in water and in cable ducts if no risk of mechanical damage is to be expected.

Download datasheet (E-AYY)
Number of conductors x 
Nominal cross-section
Insulation thickness Outer Ø Conductor resistance
at 20°C
Current carrying capacity
at 30°C in air
Current carrying capacity
at 20°C in soil
Aluminum count Central warehouse Central warehouse
mm² approx. mm approx. mm ca. Ω/km A A kg/km J O
1 x 25 RM 1,2 11,0 1,2 87,0 106,0 74,0
1 x 35 RM 1,2 12,0 0,868 107,0 127,0 103,0
1 x 50 RM 1,4 14,0 0,641 131,0 151,0 147,0
1 x 70 RM 1,4 16,0 0,443 166,0 185,0 206,0
1 x 95 RM 1,6 18,0 0,32 205,0 222,0 279,0
1 x 120 RM 1,6 19,0 0,253 239,0 253,0 353,0
1 x 150 RM 1,8 21,0 0,206 273,0 284,0 441,0
1 x 185 RM 2,0 24,0 0,164 317,0 322,0 544,0
1 x 240 RM 2,2 26,0 0,125 378,0 375,0 706,0
1 x 300 RM 2,4 29,0 0,1 437,0 425,0 882,0
1 x 400 RM 2,6 32,0 0,0778 513,0 487,0 1.200,0
1 x 500 RM 2,8 36,0 0,0605 600,0 558,0 1.510,0
1 x 630 RM 2,8 40,0 0,0469 701,0 635,0 1.900,0
3 x 150/70 SM 1,8/1,4 44,0 0,206/0,443 246,0 275,0 1.529,0
3 x 185/95 SM 2,0/1,6 47,0 0,164/0,320 285,0 313,0 1.911,0
3 x 240/120 SM 2,2/1,6 55,0 0,125/0,253 338,0 364,0 2.470,0
4 x 16 RM 1,2 23,0 1,9 50,0 63,0 189,0
4 x 25 RM 1,2 25,0 1,2 82,0 102,0 294,0
4 x 35 SM 1,2 27,0 0,868 100,0 123,0 412,0
4 x 50 SM 1,4 27,0 0,641 119,0 144,0 588,0
4 x 70 SM 1,4 30,0 0,443 152,0 179,0 823,0
4 x 95 SM 1,6 34,0 0,32 186,0 215,0 1.117,0
4 x 120 SM 1,6 40,0 0,253 216,0 245,0 1.411,0
4 x 150 SM 1,8 43,0 0,206 246,0 275,0 1.764,0
4 x 185 SM 2,0 50,0 0,164 285,0 313,0 2.176,0
4 x 240 SM 2,2 54,0 0,125 338,0 364,0 2.822,0
4 x 300 SM 2,4 58,0 0,1 400,0 419,0 3.528,0
5 x 10 RE 1,0 22,0 0,94 34,0 47,0 147,0
5 x 16 RM 1,2 24,0 1,9 50,0 63,0 235,0
5 x 25 RM 1,2 26,0 1,2 82,0 102,0 368,0
5 x 25 SM 1,2 26,0 1,2 82,0 102,0 368,0
5 x 35 RM 1,2 28,0 0,868 100,0 123,0 515,0
5 x 35 SM 1,2 28,0 0,868 100,0 123,0 515,0
5 x 50 RM 1,4 30,0 0,641 119,0 144,0 781,0
5 x 50 SM 1,4 30,0 0,641 119,0 144,0 781,0
5 x 70 RM 1,4 34,0 0,443 152,0 179,0 1.071,0
5 x 70 SM 1,4 34,0 0,443 152,0 179,0 1.071,0
5 x 95 RM 1,6 38,0 0,32 186,0 215,0 1.484,0
5 x 95 SM 1,6 38,0 0,32 186,0 215,0 1.484,0
5 x 120 RM 1,6 45,0 0,253 216,0 245,0 1.875,0
5 x 120 SM 1,6 45,0 0,253 216,0 245,0 1.875,0
5 x 150 RM 1,8 48,0 0,206 246,0 275,0 2.343,0
5 x 150 SM 1,8 48,0 0,206 246,0 275,0 2.343,0
5 x 185 RM 2,0 56,0 0,164 285,0 313,0 2.891,0
5 x 185 SM 2,0 56,0 0,164 285,0 313,0 2.891,0
5 x 240 RM 2,2 60,0 0,125 338,0 364,0 3.744,0
5 x 240 SM 2,2 60,0 0,125 338,0 364,0 3.744,0

ÖVE K23 and K603/HD 603 S1

  • bare aluminium conductor, solid (RE/SE)
    according to DIN VDE 0295 cl.1, IEC 60228 cl.1
    or stranded (RM/SM)
    according to DIN VDE 0295 cl.2, IEC 60228 cl.2
  • PVC - core insulation DIV 4
  • Core labelling according to HD 308 S2
  • PVC filling coat (FM) or banding (BD)
  • PVC outer sheath DMV 5
  • Sheath colour black
Nominal voltage U₀/U: 0,6/1 kV
Testing voltage: 4000 V
Temperature range:
When laying: max. -5°C
Operating temperature: -30°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +160°C/5 sec.
Minimum bending radius:
single core: 15 x DA
multicore: 12 x DA
CPR performance class: Eca