H07V2-K

header edlersystems cable2 min v4
UL-Leitungen
H07V2-K

For the internal wiring of switch cabinets, electrical appliances, e.g. television, radio or household appliances, control panels and as a connecting cable for machines in protective conduits and tubes, as well as a connecting cable for motors and transformers.

Download datasheet (H05V2-K / H07V2-K)
Nominal cross-section Colors Conductor structure Outer Ø Weight Cu count Central warehouse Factory warehouse
mm² approx. mm approx. mm approx. kg/km kg/km
AWG 16 (1,5)
30 x 0,25 3,2 21,0 15,0
AWG 16 (1,5)
30 x 0,25 3,2 21,0 15,0
AWG 14 (2,5)
50 x 0,25 3,6 29,9 25,0
AWG 14 (2,5)
50 x 0,25 3,6 29,9 25,0
AWG 12 (4,0)
56 x 0,30 4,2 46,1 40,0
AWG 10 (6,0)
84 x 0,30 4,8 66,1 60,0
AWG 8 (10,0)
80 x 0,40 6,4 114,2 100,0
AWG 6 (16,0)
126 x 0,40 8,8 192,3 160,0
AWG 4 (25,0)
196 x 0,40 10,0 269,7 250,0
AWG 2 (35,0)
276 x 0,40 11,5 367,3 350,0
AWG 1 (50,0)
400 x 0,40 14,0 550,0 500,0
AWG 2/0 (70,0)
356 x 0,50 16,5 752,0 700,0
AWG 3/0 (95,0)
485 x 0,50 17,8 1.126,0 950,0
AWG 4/0 (120,0)
614 x 0,5 19,4 1.215,0 1.200,0

UL/CSA/HAR

  • Stranded copper wire, tinned, finely stranded according to DIN VDE 0295 cl.5,
    IEC 60228 cl.5
  • PVC core insulation according to UL standard 1581 Tab.50.182
Operating voltage U:
H05V2-K: 300/500 V
UL/CSA 1007/1569: 300 V
H07V2-K: 450/750 V
CSA+UL (MTW): 600 V
UL(AWM) (10269): 1000 V
Testing voltage: 3000 V
Operating temperature:
HAR: -40°C to +90°C
UL (MTW): -40°C to +90°C
CSA+UL(AWM): -40°C to +105°C
Minimum bending radius:
When laying: 15 x DA
Fixed installation: 10 x DA
Fire behaviour: UL VW-1, CSA FT1
CPR performance class: Eca