YM

header edlersystems cable2 min v4
PVC-Mantelleitung
YM

For industrial and domestic installations, in dry, damp and wet rooms, on, in and under plaster, as well as in masonry and concrete, except for direct embedding in vibrated or tamped concrete. This cable is not suitable for laying directly in the ground. Outdoor use is only possible if it is protected from direct sunlight.

Download datasheet (YM)
Number of conductors x 
Nominal cross-section
Conductor Ø Insulation thickness Outer Ø Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Cu count Central warehouse Central warehouse
mm² approx. mm approx. mm approx. mm approx. kg/km ca. Ω/km A kg/km J O
2 x 1,5 RE 1,5 0,6 8,5 100,0 12,1 14,0 30,0
3 x 1,5 RE 1,5 0,6 8,8 120,0 12,1 14,0 45,0
4 x 1,5 RE 1,5 0,6 9,6 140,0 12,1 14,0 60,0
5 x 1,5 RE 1,5 0,6 10,3 170,0 12,1 14,0 75,0
7 x 1,5 RE 1,5 0,6 11,3 210,0 12,1 14,0 105,0
7 x 1,5 RE färb. Adern 1,5 0,6 11,3 210,0 12,1 14,0 105,0
10 x 1,5 RE 1,5 0,6 14,7 330,0 12,1 14,0 150,0
12 x 1,5 RE 1,5 0,6 16,0 400,0 12,1 14,0 180,0
2 x 2,5 RE 1,9 0,7 9,5 145,0 7,4 18,0 50,0
3 x 2,5 RE 1,9 0,7 10,4 165,0 7,4 18,0 75,0
4 x 2,5 RE 1,9 0,7 11,2 200,0 7,4 18,0 100,0
5 x 2,5 RE 1,9 0,7 12,1 245,0 7,4 18,0 125,0
7 x 2,5 RE 1,9 0,7 14,5 320,0 7,4 18,0 175,0
3 x 4 RE 2,4 0,8 11,5 240,0 4,6 24,0 120,0
4 x 4 RE 2,4 0,8 13,2 305,0 4,6 24,0 160,0
5 x 4 RE 2,4 0,8 14,7 370,0 4,6 24,0 200,0
3 x 6 RE 2,9 0,8 13,0 330,0 3,1 31,0 180,0
4 x 6 RE 2,9 0,8 14,8 400,0 3,1 31,0 240,0
5 x 6 RE 2,9 0,8 16,1 495,0 3,1 31,0 300,0
4 x 10 RE 3,7 1,0 17,8 635,0 1,8 41,0 400,0
4 x 10 RM 4,2 1,0 17,8 635,0 1,8 41,0 400,0
5 x 10 RE 3,7 1,0 19,3 770,0 1,8 41,0 500,0
5 x 10 RM 4,2 1,0 19,3 770,0 1,8 41,0 500,0
4 x 16 RM 5,3 1,0 21,8 915,0 1,2 55,0 640,0
5 x 16 RM 5,3 1,0 23,2 1.150,0 1,2 55,0 800,0
3 x 1,5 RE ROT 1,5 0,6 8,8 120,0 12,1 14,0 45,0
3 x 1,5 RE GRÜN 1,5 0,6 8,8 120,0 12,1 14,0 45,0
3 x 2,5 RE ROT 1,9 0,7 10,4 165,0 7,4 18,0 75,0

         ÖNORM E 8242

  • Bare copper wire, solid (RE) to DIN VDE 0295 cl.1,
    IEC 60228 cl.1 or stranded (RM) to DIN VDE 0295 cl.2, IEC 60228 cl.2
  • PVC – core insulation TI1
  • Core labelling according to HD 308 S2
  • Cores stranded in layers with optimum lay lengths
  • Filling coat
  • PVC – Outer sheath TM1
  • Sheath colour grey
Nominal voltage U₀/U: 300/500 V
Testing voltage: 2000 V
Insulating resistance: ≥ 20 MOhm x km
Temperature range:
When laying: min. +5°C
Operating temperature: -40°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +160°C/5 sec.
Minimum bending radius: 4x DA
CPR performance class: Eca