(N)YM(St)-J

header edlersystems cable2 min v4
PVC-Mantelleitung
(N)YM(St)-J

For effective limitation of electromagnetic interference fields, especially for installation in the computer sector, in hospitals or in industry. In conjunction with particularly interference-sensitive measuring devices for laying on, in and under plaster in dry and damp rooms as well as in concrete and masonry, except for direct embedding in vibrated concrete. This cable is not suitable for laying directly in the ground. Outdoor use is only possible if it is protected from direct sunlight.

Download datasheet ((N)YM(St)-J)
Number of conductors x 
Nominal cross-section
Conductor Ø Insulation thickness Outer Ø Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Cu count Central warehouse Factory warehouse
mm² approx. mm approx. mm approx. mm approx. kg/km ca. Ω/km A kg/km J J
3 x 1,5/1,5 1,4 0,6 9,8 158,0 12,1 14,0 55,0
4 x 1,5/1,5 1,4 0,6 10,2 177,0 12,1 14,0 68,0
5 x 1,5/1,5 1,4 0,6 11,2 216,0 12,1 14,0 83,0
7 x 1,5/1,5 1,4 0,6 11,7 247,0 12,1 14,0 113,0
3 x 2,5/1,5 1,8 0,7 10,9 208,0 7,4 18,0 83,0
5 x 2,5/1,5 1,8 0,7 12,6 291,0 7,4 18,0 133,0

based on DIN VDE 0250-204

  • Bare copper wire, solid (RE) according to DIN VDE 0295 cl.1,
    IEC 60228 cl.1
  • PVC core insulation TI1
  • Core labelling according to HD 308 S2
  • Foil shielding made of coated aluminium foil
    with tinned drain wire
  • PVC outer sheath
  • Sheath colour grey
Nominal voltage U₀/U: 300/500 V
Testing voltage: 2000 V
Insulating resistance: ≥ 20 MOhm x km
Temperature range:
When laying: min. +5°C
Operating temperature: -40°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +160°C/5 sec.
Minimum bending radius: 4x DA
CPR performance class: Eca