H05V-U

header edlersystems cable2 min v4
PVC core cable
H05V-U

These cables are used for the internal wiring of devices, switchgear and distribution boards as well as for installation in and on luminaires with a rated voltage of up to 1000 V or a DC voltage of up to 750 V to earth.

In dry rooms, in switchgear and distribution systems for laying in conduit on and under plaster as well as without conduit on suitable insulating bodies.

Download datasheet (H05V-U / H07V-U)
Nominal cross-section Colors Conductor Ø Insulation thickness Outer Ø (min - max)
min - max
Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Cu count Central warehouse Factory warehouse
mm² approx. mm approx. mm mm approx. kg/km ca. Ω/km A kg/km
0,5
0,77 0,6 1,9 - 2,3 9,0 36,0 12,0 5,0
0,5
0,77 0,6 1,9 - 2,3 9,0 36,0 12,0 5,0
0,75
0,95 0,6 2,1 - 2,5 12,0 24,5 15,0 7,5
0,75
0,95 0,6 2,1 - 2,5 12,0 24,5 15,0 7,5
0,75
0,95 0,6 2,1 - 2,5 12,0 24,5 15,0 7,5
1,0
1,2 0,6 2,2 - 2,7 14,0 18,1 15,0 10,0
1,0
1,2 0,6 2,2 - 2,7 14,0 18,1 15,0 10,0
1,0
1,2 0,6 2,2 - 2,7 14,0 18,1 15,0 10,0

DIN VDE 0285-525-2-31 / DIN EN 50525-2-31 HD 21.3.S3

  • Bare copper wire, solid (RE) according to DIN VDE 0295 cl.1, IEC 60228 cl.1
  • PVC core insulation TI1
Nominal voltage U0/U EN: H05V-U: 300/500 V, H07V-U: 450/750 V
H05V-U: 300/500 V
H07V-U: 450/750 V
Testing voltage: H05V-U: 2000 V, H07V-U: 2500 V
H05V-U: 2000 V
H07V-U: 2500 V
Insulating resistance: ≥ 10 MOhm x km
Temperature range: when laying: min. +5°C, Operating temperature: -40°C to +70°C
When laying: min. +5°C
Operating temperature: -40°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +160°C/5 sec.
Minimum bending radius: 4 x DA
CPR performance class: Eca