H05V-K

header edlersystems cable2 min v4
PVC core cable
H05V-K

Approved for the internal wiring of devices, distributors or switchgear as well as for protected installation in and on luminaires with a rated voltage of up to 1000 V AC or a DC voltage of up to 750 V to earth. Also suitable for laying in conduits on, in and under plaster as well as in closed installation ducts. Not suitable for direct installation on platforms, channels or trays.

Download datasheet (H05V-K / H07V-K)
Nominal cross-section Colors Conductor structure Insulation thickness Outer Ø (min - max)
min - max
Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Cu count Central warehouse Factory warehouse
mm² approx. mm approx. mm mm approx. kg/km ca. Ω/km A kg/km
0,5
16 x 0,20 0,6 2,1 - 2,5 10,0 39,0 12,0 5,0
0,5
16 x 0,20 0,6 2,1 - 2,5 10,0 39,0 12,0 5,0
0,5
16 x 0,20 0,6 2,1 - 2,5 10,0 39,0 12,0 5,0
0,75
24 x 0,20 0,6 2,2 - 2,7 12,0 26,0 15,0 7,5
0,75
24 x 0,20 0,6 2,2 - 2,7 12,0 26,0 15,0 7,5
1,0
32 x 0,20 0,6 2,4 - 2,8 14,0 19,5 19,0 10,0
1,0
32 x 0,20 0,6 2,4 - 2,8 14,0 19,5 19,0 10,0

DIN VDE 0285-525-2-31/DIN EN 50525-2-31/HD 21.3.S3

  • Bare copper stranded wire, finely stranded according to DIN VDE 0295 cl.5,
    IEC 60228 cl.5
  • PVC – wire insulation TI1 
Nominal voltage U₀/U:
H05V-K: 300/500 V
H07V-K: 450/750 V
Testing voltage:
H05V-K: 2000 V
H07V-K: 2500 V
Insulating resistance: ≥ 10 MOhm x km
Temperature range:
When laying: min. +5°C
Operating temperature: -40°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +160°C/5 sec.
Minimum bending radius: 4 x DA to 16 mm²
5 x DA 25 to 50 mm²
6 x DA from 70 mm²
CPR performance class: Eca