H05VVH6-F

header edlersystems cable2 min v4
Kran- und Hebezeugleitungen
H05VVH6-F

For low and medium mechanical stress for connecting moving parts of machine tools, conveyor systems and large appliances, provided the cable is only moved in one plane. For use in dry, damp and wet rooms as well as outdoors.

Download datasheet (H05VVH6-F / H07VVH6-F)
Number of conductors x 
Nominal cross-section
Conductor structure Dimensions 
Height x Width
Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Cu count Central warehouse Factory warehouse
mm² approx. mm approx. mm approx. kg/km ca. Ω/km A kg/km G G
4 G 0,75 24 x 0,21 4,6 x 12,8 100,0 26,0 6,0 30,0
5 G 0,75 24 x 0,21 4,6 x 16,1 141,0 26,0 6,0 37,5
8 G 0,75 24 x 0,21 4,6 x 25,9 190,0 26,0 6,0 60,0
12 G 0,75 24 x 0,21 4,6 x 32,6 260,0 26,0 6,0 90,0
18 G 0,75 24 x 0,21 4,6 x 48,0 400,0 26,0 6,0 135,0
24 G 0,75 24 x 0,21 4,6 x 63,2 510,0 26,0 6,0 180,0
4 G 1 32 x 0,21 4,8 x 13,8 115,0 19,5 10,0 40,0
5 G 1 32 x 0,21 4,8 x 16,3 135,0 19,5 10,0 50,0
8 G 1 32 x 0,21 4,8 x 26,9 220,0 19,5 10,0 80,0
12 G 1 32 x 0,21 4,8 x 35,2 310,0 19,5 10,0 120,0
18 G 1 32 x 0,21 4,8 x 53,4 470,0 19,5 10,0 180,0
24 G 1 32 x 0,21 4,8 x 68,1 600,0 19,5 10,0 240,0

DIN VDE 0283-2

  • Bare copper conductor, fine stranded according to DIN VDE 0295 cl.5,
    IEC 60228 cl.5
  • PVC – core insulation TI2
  • Cores arranged flat next to each other
  • Core labelling according to HD 308 S2
    from 7-core version black with numbers
  • PVC – outer sheath TM2
  • Sheath colour black (RAL 9005)
Nominal voltage U₀/U:
H05VVH6-F: 300/500 V
H07VVH6-F: 450/750 V
Testing voltage:
H05VVH6-F: 2000 V
H07VVH6-F: 2500 V
Insulating resistance: ≥ 20 MOhm x km
Temperature range:
When laying: max. -5°C
Operating temperature: -30°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: +160°C/5 sec.
Minimum bending radius: 10 x DA
Fire behaviour: EN 60332-1-2
IEC 60332-1