NGFLGöu

header edlersystems cable2 min v4
Gummileitungen
NGFLGöu

Neoprener flat cables are mainly used as trailing cables for crane systems, floor conveyors and storage and retrieval machines. For medium mechanical stress for connecting moving parts of machine tools, conveyor systems and large appliances, provided the cable is only moved in one plane. These cables are weatherproof and can be used under the harshest environmental conditions.

Download datasheet (NGFLGöu)
Number of conductors x 
Nominal cross-section
Conductor Ø Dimensions 
Height x Width
Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Cu count Central warehouse Factory warehouse
mm² approx. mm approx. mm approx. kg/km ca. Ω/km A kg/km G G
4 G 1,5 1,5 6,2 x 15,8 171,0 13,3 18,0 60,0
5 G 1,5 1,5 6,0 x 20,1 214,0 13,3 18,0 75,0
7 G 1,5 1,5 6,0 x 26,8 292,0 13,3 18,0 105,0
8 G 1,5 1,5 6,0 x 28,3 325,0 13,3 18,0 120,0
12 G 1,5 1,5 6,8 x 43,5 550,0 13,3 18,0 180,0
24 G 1,5 1,5 12,1 x 52,7 1.050,0 13,3 18,0 360,0
4 G 2,5 2,0 7,4 x 19,6 257,0 8,0 26,0 100,0
5 G 2,5 2,0 7,4 x 24,6 332,0 8,0 26,0 125,0
7 G 2,5 2,0 7,4 x 32,8 452,0 8,0 26,0 175,0
8 G 2,5 2,0 7,4 x 35,9 510,0 8,0 26,0 200,0
12 G 2,5 2,0 8,0 x 53,5 810,0 8,0 26,0 300,0
24 G 2,5 2,0 15,8 x 69,2 1.730,0 8,0 26,0 600,0
4 G 4 2,8 9,0 x 24,0 402,0 5,0 34,0 160,0
5 G 4 2,8 9,0 x 31,2 510,0 5,0 34,0 200,0
7 G 4 2,8 9,0 x 40,9 720,0 5,0 34,0 280,0
4 G 6 3,5 9,6 x 27,0 510,0 3,3 44,0 240,0
5 G 6 3,5 9,6 x 39,1 640,0 3,3 44,0 300,0
7 G 6 3,5 9,6 x 45,3 910,0 3,3 44,0 420,0
4 G 10 4,5 11,3 x 32,8 770,0 1,9 61,0 400,0
5 G 10 4,5 11,3 x 41,6 960,0 1,9 61,0 500,0
7 G 10 4,5 11,3 x 55,9 1.370,0 1,9 61,0 700,0
4 G 16 5,6 13,0 x 37,6 1.160,0 1,2 82,0 640,0
5 G 16 5,6 12,7 x 47,6 1.370,0 1,2 82,0 800,0
4 G 25 6,6 14,5 x 43,8 1.560,0 0,78 108,0 1.000,0
5 G 25 6,6 16,0 x 60,0 2.215,0 0,78 108,0 1.250,0
4 G 35 8,1 16,8 x 50,3 2.100,0 0,554 135,0 1.400,0
4 G 50 9,7 19,3 x 59,0 2.930,0 0,386 168,0 2.000,0
4 G 70 11,2 21,5 x 66,0 3.910,0 0,272 207,0 2.800,0
4 G 95 13,1 24,5 x 76,2 5.120,0 0,206 250,0 3.800,0

DIN VDE 0250-809

  • Bare copper stranded wire, 1,5 to 25 mm² extra-fine stranded according to
    DIN VDE 0295 cl.6, IEC 60228 cl.6 from 35 mm² fine stranded
    according to DIN VDE 0295 cl.5, IEC 602228 cl.5
  • Special rubber core insulation 3GI3
  • Core labelling according to HD 308 S2
    from 7-core version black with numbers
  • Cores arranged flat next to each other
  • Neoprene outer sheath 5GM3
  • Sheath colour black
Nominal voltage U₀/U: 300/500 V
Testing voltage: 2000 V
Insulating resistance: ≥ 10 MOhm x km
Temperature range:
When laying: max. -25°C
Operating temperature: -40°C to +80°C
Conductor operating temperature: max. +90°C
Short-circuit temperature: +200°C/5 sec.
Minimum bending radius:
When laying: 10 x DA
Fixed installation: 5 x DA
Fire behaviour: EN 60332-1-2
IEC 60332-1