For medium mechanical stress as a flexible power and control cable for connecting moving parts such as control bulbs for crane control in dry, damp and wet rooms as well as outdoors. However, the cable is not suitable for use on rollers or reels under tensile load.

Download datasheet ((N)FLGöu)
Number of conductors x 
Nominal cross-section
Conductor structure Outer Ø Weight Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Cu count Central warehouse Factory warehouse
mm² approx. mm approx. mm approx. kg/km ca. Ω/km A kg/km G G
7 G 1 56 x 0,16 14,0 225,0 19,5 13,0 70,0
12 G 1 56 x 0,16 18,9 400,0 19,5 13,0 120,0
18 G 1 56 x 0,16 19,8 490,0 19,5 13,0 180,0
24 G 1 56 x 0,16 22,5 650,0 19,5 13,0 240,0
36 G 1 56 x 0,16 27,0 980,0 19,5 13,0 360,0
48 G 1 56 x 0,16 31,0 1.235,0 19,5 13,0 480,0
4 G 1,5 84 x 0,16 11,0 171,0 13,3 16,0 60,0
5G 1,5 84 x 0,16 12,0 223,0 13,3 16,0 75,0
7 G 1,5 84 x 0,16 14,0 270,0 13,3 16,0 105,0
9 G 1,5 84 x 0,16 17,0 410,0 13,3 16,0 135,0
12 G 1,5 84 x 0,16 19,5 510,0 13,3 16,0 180,0
18 G 1,5 84 x 0,16 21,0 630,0 13,3 16,0 270,0
24 G 1,5 84 x 0,16 23,5 910,0 13,3 16,0 360,0
4 G 2,5 140 x 0,16 12,0 250,0 8,0 21,0 100,0
7 G 2,5 140 x 0,16 15,5 380,0 8,0 21,0 175,0
12 G 2,5 140 x 0,16 22,0 710,0 8,0 21,0 300,0

based on DIN VDE 0250

  • Supporting element made of banded cord or synthetic rope
  • Bare copper stranded wire, extra-fine stranded
    according to DIN VDE 0295 cl.6, IEC 60228 cl.6
  • Rubber core insulation
  • cores with optimum lay lengths in layers around
    stranded around the supporting element in the core
  • Banding over each stranding layer
  • Core labelling according to HD 308 S2
    from 7-core version black with numbers
  • Neoprene outer sheath
  • Sheath colour black
Nominal voltage U₀/U: 300/500 V
Testing voltage: 3000 V
Insulating resistance: ≥ 10 MOhm x km
Temperature range:
When laying: max. -25°C
Operating temperature: -40°C to +80°C
Conductor operating temperature: max. +80°C
Short-circuit temperature: max. +150°C/5 sec.
Minimum bending radius: 12,5 x DA
Fire behaviour: EN 60332-1-2
IEC 60332-1