XYMM
For connecting equipment, especially on construction sites. In dry and damp rooms, outdoors and in potentially explosive atmospheres.
Cable is only authorised for the Austrian market.
Download datasheet (XYMM)
For connecting equipment, especially on construction sites. In dry and damp rooms, outdoors and in potentially explosive atmospheres.
Cable is only authorised for the Austrian market.
Number of conductors x Nominal cross-section |
Conductor structure | Outer Ø | Weight |
Conductor resistance at 20°C |
Cu count | Central warehouse | Central warehouse |
---|---|---|---|---|---|---|---|
mm² | approx. mm | approx. mm | approx. kg/km | ca. Ω/km | kg/km | G | x |
2 x 1,5 | 30 x 0,26 | 8,0 | 80,0 | 13,3 | 30,0 | ||
3 G 1,5 | 30 x 0,26 | 8,6 | 98,0 | 13,3 | 45,0 | ||
4 G 1,5 | 30 x 0,26 | 9,6 | 127,0 | 13,3 | 60,0 | ||
5 G 1,5 | 30 x 0,26 | 10,6 | 158,0 | 13,3 | 75,0 | ||
3 G 2,5 | 50 x 0,26 | 10,2 | 152,0 | 8,0 | 75,0 | ||
4 G 2,5 | 50 x 0,26 | 11,2 | 192,0 | 8,0 | 100,0 | ||
5 G 2,5 | 50 x 0,26 | 12,4 | 234,0 | 8,0 | 125,0 | ||
5 G 4 | 56 x 0,31 | 14,9 | 356,0 | 5,0 | 200,0 | ||
5 G 6 | 84 x 0,31 | 16,6 | 480,0 | 3,3 | 300,0 | ||
5 G 10 | 80 x 0,41 | 20,7 | 795,0 | 1,9 | 500,0 | ||
5 G 16 | 128 x 0,41 | 23,4 | 1.122,0 | 1,2 | 800,0 |
based on EN 50525-1
Nominal voltage U₀/U: | 450/750 V |
Testing voltage: | 2500 V |
Temperature range: | |
When laying: | max. -35°C |
Operating temperature: | -35°C to +70°C |
Conductor operating temperature: | max. +70°C |
Short-circuit temperature: | max. +150°C/5 sec |
Minimum bending radius: | 5 x DA |
CPR performance class: | Eca |