XYMM

header edlersystems cable2 min v4
Baustellen- und Purleitungen
XYMM

For connecting equipment, especially on construction sites. In dry and damp rooms, outdoors and in potentially explosive atmospheres.
Cable is only authorised for the Austrian market.

Download datasheet (XYMM)
Number of conductors x 
Nominal cross-section
Conductor structure Outer Ø Weight Conductor resistance
at 20°C
Cu count Central warehouse Central warehouse
mm² approx. mm approx. mm approx. kg/km ca. Ω/km kg/km G x
2 x 1,5 30 x 0,26 8,0 80,0 13,3 30,0
3 G 1,5 30 x 0,26 8,6 98,0 13,3 45,0
4 G 1,5 30 x 0,26 9,6 127,0 13,3 60,0
5 G 1,5 30 x 0,26 10,6 158,0 13,3 75,0
3 G 2,5 50 x 0,26 10,2 152,0 8,0 75,0
4 G 2,5 50 x 0,26 11,2 192,0 8,0 100,0
5 G 2,5 50 x 0,26 12,4 234,0 8,0 125,0
5 G 4 56 x 0,31 14,9 356,0 5,0 200,0
5 G 6 84 x 0,31 16,6 480,0 3,3 300,0
5 G 10 80 x 0,41 20,7 795,0 1,9 500,0
5 G 16 128 x 0,41 23,4 1.122,0 1,2 800,0

based on EN 50525-1

  • Bare copper stranded wire, fine stranded according to DIN VDE 0295 cl.5,
    IEC 60228 cl. 5
  • PVC – core insulation (cold-resistant)
  • Core labelling according to HD 308 S2
  • PVC – Aussenmantel (cold-resistant)
  • Sheath colour yellow
Nominal voltage U₀/U: 450/750 V
Testing voltage: 2500 V
Temperature range:
When laying: max. -35°C
Operating temperature: -35°C to +70°C
Conductor operating temperature: max. +70°C
Short-circuit temperature: max. +150°C/5 sec
Minimum bending radius: 5 x DA
CPR performance class: Eca