H07BQ-F

header edlersystems cable2 min v4
Baustellen- und Purleitungen
H07BQ-F

In dry and damp rooms as well as outdoors for short periods under medium mechanical stress. As a tool connection cable with high oil resistance, abrasion resistance and notch resistance.

Download datasheet (H05BQ-F / H07BQ-F)
Number of conductors x 
Nominal cross-section
Conductor structure Insulation thickness Outer Ø (min - max)
min - max
Conductor resistance
at 20°C
Current carrying capacity
at 30°C
Cu count Central warehouse Central warehouse Factory warehouse Factory warehouse
mm² approx. mm approx. mm mm ca. Ω/km A kg/km G x G x
2 x 1,5 30 x 0,26 0,8 7,6 - 9,8 13,3 16,0 30,0
3 G 1,5 30 x 0,26 0,8 8,0 - 10,4 13,3 16,0 45,0
4 G 1,5 30 x 0,26 0,8 9,0 - 11,6 13,3 18,0 60,0
5 G 1,5 30 x 0,26 0,8 9,8 - 12,7 13,3 18,0 75,0
3 G 2,5 50 x 0,26 0,9 9,6 - 12,4 8,0 21,0 75,0
4 G 2,5 50 x 0,26 0,9 10,7 - 13,8 8,0 26,0 100,0
5 G 2,5 50 x 0,26 0,9 11,9 - 15,3 8,0 26,0 125,0
4 G 4 56 x 0,31 1,0 12,7 - 16,2 5,0 34,0 160,0
5 G 4 56 x 0,31 1,0 14,1 - 17,9 5,0 34,0 200,0
4 G 6 84 x 0,31 1,0 15,2 - 18,8 3,3 44,0 240,0
5 G 6 84 x 0,31 1,0 15,7 - 20,0 3,3 44,0 300,0
5 G 10 80 x 0,41 1,2 20,4 - 25,9 1,9 61,0 500,0
5 G 16 128 x 0,41 1,2 23,7 - 30,0 1,2 82,0 800,0
5 G 25 200 x 0,41 1,4 30,5 - 36,2 0,78 109,0 1.250,0

DIN VDE 0285-525-2-21
except X07BQ-F based on DIN VDE 0285-525-2-21

  • Bare copper stranded wire, fine stranded according to DIN VDE 0295 cl.5,
    IEC 60228 cl.5
  • Rubber core insulation, EI6
  • Core labelling according to HD 308 S2
    from 7-core version black with numbers
  • Cores stranded in layers with optimum lay lengths
    (inner protective sheath permissible)
  • PUR – outer sheath TMPU
  • Sheath colour orange (RAL 2003)

Special properties:

  • abrasion resistant
  • notch resistant
  • tear and cut resistant
Nominal voltage U₀/U:
H05BQ-F: 300/500 V
H07BQ-F: 450/750 V
Conductor operating temperature: max. +90°C
Testing voltage:
H05BQ-F: 2000 V
H07BQ-F: 2500 V
Temperature range:
When laying: max. -40°C
Operating temperature: -40°C to +80°C
Short-circuit temperature: max. 200°C/5 sec.
Minimum bending radius:
When laying: 5 x DA
Fixed installation: 3 x DA
Fire behaviour:
H05BQ-F: EN 60332-1-2
IEC 60332-1
CPR performance class:
H07BQ-F: Eca