F-YAY

header edlersystems cable2 min v4
Fernmeldekabel zur Innenverlegung
F-YAY

As installation cable for telecommunication purposes inside buildings in dry and damp rooms on, in and under plaster, but also outdoors for fixed installation on external walls of buildings with protection from sunlight. Not authorised for heavy current installation purposes and underground laying.

Download datasheet (F-YAY)
Number of conductors x 
Nominal cross-section
Sheath thickness Outer Ø Weight Cu count Central warehouse
mm approx. mm approx. mm approx. kg/km kg/km
2 x 2 x 0,6 1,0 5,9 41,0 13,0
3 x 2 x 0,6 1,0 6,1 49,0 19,0
5 x 2 x 0,6 1,0 7,1 69,0 30,0
6 x 2 x 0,6 1,0 7,6 77,0 36,0
10 x 2 x 0,6 1,0 8,8 112,0 59,0
15 x 2 x 0,6 1,0 10,4 152,0 87,0
20 x 2 x 0,6 1,2 11,5 185,0 115,0
25 x 2 x 0,6 1,2 13,5 244,0 140,0
30 x 2 x 0,6 1,2 14,0 290,0 172,0
40 x 2 x 0,6 1,2 15,0 370,0 228,0
50 x 2 x 0,6 1,4 17,5 430,0 285,0
60 x 2 x 0,6 1,4 18,9 525,0 342,0
100 x 2 x 0,6 1,6 24,7 805,0 568,0
2 x 2 x 0,8 1,0 7,3 61,0 21,0
3 x 2 x 0,8 1,0 7,9 75,0 32,0
5 x 2 x 0,8 1,0 9,4 115,0 52,0
6 x 2 x 0,8 1,0 10,3 138,0 62,0
10 x 2 x 0,8 1,2 11,9 187,0 103,0
20 x 2 x 0,8 1,2 15,3 340,0 203,0
30 x 2 x 0,8 1,4 17,7 497,0 304,0
40 x 2 x 0,8 1,4 20,4 681,0 404,0
50 x 2 x 0,8 1,6 24,9 830,0 505,0
100 x 2 x 0,8 1,8 34,0 1.570,0 1.008,0

ÖVE K 35

  • Bare copper wire, solid, Ø 0,6 mm and Ø 0,8 mm
  • PVC - core insulation
  • Core labelling according to ÖVE K 35
  • Cores twisted into pairs, pairs twisted into layers
  • Strapping made of plastic film
  • Shield made of plastic-laminated aluminium foil with drain wire
  • PVC outer sheath
  • Sheath colour grey (RAL 7035)
Operating voltage U: max. 300 V
Testing voltage (50 Hz):
Core/Core: 500 V
Core/Shield: 2000 V
Insulating resistance: ≥ 500 MOhm x km
Conductor resistance of the loop:
Ø 0,6 mm: max. 135,8 Ohm/km
Ø 0,8 mm: max. 73,2 Ohm/km
Operating capacity (at 800 Hz): max. 100 nF/km
Capacitive coupling (at 800 Hz): max. 500 pF/ 100m
Temperature range:
When laying: max. -5°C
Operating temperature: -30°C to +70°C
Minimum bending radius: 7,5 x DA
CPR performance class: Eca