AJ-Y(St)YDY / 16

header edlersystems cable2 min v4
Fernmeldekabel zur Außenverlegung
AJ-Y(St)YDY / 16

For signal transmission in telecommunication systems or measurement, control, data and regulation technology systems. Suitable for fixed installation indoors, outdoors and in the ground.

Download datasheet (AJ-Y(ST)YDY BD Si)
Number of conductors x 
Nominal cross-section
Sheath thickness Outer Ø Weight Loop conductor resistance Cu count Central warehouse Factory warehouse
mm approx. mm approx. mm approx. kg/km max. Ω/km kg/km
2 x 2 x 0,8 1,8 12,7 330,0 73,2 201,0
4 x 2 x 0,8 1,8 15,0 380,0 73,2 222,0
8 x 2 x 0,8 1,8 17,5 480,0 73,2 264,0
12 x 2 x 0,8 1,8 18,5 495,0 73,2 306,0
20 x 2 x 0,8 1,8 21,0 730,0 73,2 390,0
32 x 2 x 0,8 2,0 26,5 960,0 73,2 516,0
40 x 2 x 0,8 2,0 28,0 1.150,0 73,2 599,0

according to factory standard

  • Bare copper wire, solid Ø 0,8 mm
  • PVC – core insulation
  • core labelling according to VDE 0815
  • 2 cores to a pair,
    4 pairs to bundle, bundle in layers
    (2-pair cable star quad stranded)
  • Plastic foil
  • Shield made of plastic-laminated
    aluminium foil with tinned drain wire 0.8 mm
  • PVC inner sheath
  • Shielding made of bare copper wires,
    Winding with plastic foil
  • PVC outer sheath
  • Sheath colour black
Operating voltage U: max. 225 V
Testing voltage (50 Hz):
Core/Core: 500 V
Core/Shield: 2000 V
Insulating resistance: ≥ 100 MOhm x km
Capacitive coupling (at 800 Hz): ≤ 200 pF/100m
Attenuation (at 800 Hz): ca. 1,1 dB/km
Impedance: ca. 320 Ohm
Temperature range:
When laying: max. -5°C
Operating temperature: -30°C to +70°C
Minimum bending radius:
AJ-Y(St)YDY / 16: 10 x DA
AJ-Y(St)YDY / 3,5: 15 x DA
CPR performance class: Fca