J-H(St)H EIB

header edlersystems cable2 min v4
Busleitungen
J-H(St)H EIB

For transmitting signals in building systems technology for controlling lighting, heating, air conditioning, ventilation and time recording systems. It can also be used for the transmission of measured values as an I&C cable in power installations or in process data processing. Suitable for installation on and under plaster, in pipes, in dry, damp and wet rooms and outdoors if protected from direct sunlight; not approved for power installations and underground installation.

Download datasheet (J-H(ST)H EIB)
Number of conductors x 
Nominal cross-section
Sheath color Outer Ø Weight Loop conductor resistance Cu count Central warehouse Factory warehouse
mm approx. mm approx. kg/km max. Ω/km kg/km
2 x 2 x 0,8
6,3 55,0 73,2 21,0

based on EIBA Specification

  • Bare copper wire, solid Ø 0,8 mm
  • Core insulation halogen-free polymer mixture
  • Cores and quad designation according to DIN VDE 0815
    Cores twisted to star quad
  • Shield made of plastic-laminated aluminium foil with continuity wire
  • Outer sheath made of halogen-free polymer mixture
Operating voltage U: max. 300 V
Testing voltage (50 Hz):
Core/Shield: 4000 V
Insulating resistance: 100 MOhm x km
Operating capacity (at 800 Hz): max. 100nF/km
Capacitive coupling (at 800 Hz):
K1: max. 200 pF/100m
Temperature range:
When laying: max. -5°C
Operating temperature: -30°C to +70°C
Minimum bending radius: 7,5 x DA
CPR performance class: Eca
Corrosiveness of fire gases: EN 60754-2
IEC 60754-2
Minimal smoke development: EN 61034 1+2
IEC 61034-1+2