AS-Interface-Bus

header edlersystems cable2 min v4
Busleitungen
AS-Interface-Bus

AS-Interface bus cables connect simple, binary actuators and sensors (slaves) such as proximity switches, valves or light indicators to the higher-level central control unit (master). The yellow cable is responsible for transmitting data and auxiliary power (48 V DC) for AS-Interface slaves. The black cable only transmits auxiliary power for the AS-Interface slaves (24 V DC).

Download datasheet (AS-Interface-Bus)
Number of conductors x 
Nominal cross-section
Sheath color Weight Cu count Central warehouse Factory warehouse
mm² approx. kg/km kg/km
2 x 1,5
60,0 30,0
2 x 1,5
60,0 30,0

based on AS-Interface Standard

  • Copper stranded wire, fine stranded, according to DIN VDE 0295 cl.6, IEC 60228 cl.6
  • TPE - core insulatin
  • Core colours brown and blue
  • TPE outer sheath, oil-resistant
  • Sheath colour yellow or black
Operating voltage U: max. 250 V
Testing voltage (Core/Core): 1500 V
Insulating resistance: ≥ 1 MOhm x km
Conductor resistance: max. 13,7 Ohm/km
Temperature range:
When laying: max. -5°C
Operating temperature: -40°C to +80°C
Minimum bending radius: ≥ 24 mm
Fire behaviour: EN 60332-1-2
IEC 60332-1